Bộ đổi nguồn AC/DC Din-Rail MCTT-NDR-75-12 75.6W, 12VDC, 6.3A
75W Single Output Industrial DIN Rail Power Supply NDR-75 series
Features:
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage/ Over temperature
Cooling by free air convection
Can be installed on DlN rail TS-35/7.5 or 15
UL 508 (industrial control equipment} approved
EN61000-6-2(EN50082-2} industrial immunity level
100% full load burn-in test
1 years warranty
Model |
NDR-75-12 |
NDR-75-24 |
NDR-75-48 |
Dc Voltage |
12V |
24V |
48V |
Rated Current |
6.3A |
3.2A |
1.6A |
Current Range |
0 ~ 6.3A |
0 ~ 3.2A |
0 ~ 1.6A |
Rated Power |
75.6W |
76.8W |
76.8W |
Ripple & Noise (Max.) |
80mVp-p |
120mVp-p |
150mVp-p |
Voltage Adj. Range |
12 ~ 14V |
24 ~ 28V |
48 ~ 55V |
Voltage Tolerance |
±2.0% |
±1.0% |
±1.0% |
Line Regulation |
±0.5% |
±0.5% |
±0.5% |
Load Regulation |
±1.0% |
±1.0% |
±1.0% |
Setup, Rise Time |
1200ms, 60ms/230VAC 2000ms, 60ms/115VAC at full load |
||
Hold Up Time |
60ms/230VAC 12ms/115VAC at full load |
||
Voltage Range |
90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)] |
||
Frequency Range |
47 ~ 63Hz |
||
Efficiency |
85.50% |
88% |
89% |
Ac Current |
1.45A/115VAC 0.9A/230VAC |
||
Inrush Current |
20A/115VAC 35A/230VAC |
||
Leakage Current |
<1mA / 240VAC |
||
Overload |
105 ~ 130% rated output power |
||
Protection type : Constant current limiting, recovers automatically after fault condition is removed |
|||
Over voltage |
14 ~ 17V |
29 ~ 33V |
56 ~ 65V |
Protection type : Shut down o/p voltage, re-power on to recover |
|||
Over Temperature |
Protection type : Shut down o/p voltage, re-power on to recover |
||
Working Temp. |
-20 ~ +70℃ (Refer to "Derating Curve") |
||
Working Humidity |
20 ~ 95% RH non-condensing |
||
Storage Temp., Humidity |
-40 ~ +85℃, 10 ~ 95% RH |
||
Temp. Coefficient |
±0.03%/℃ (0 ~ 50℃) |
||
Vibration |
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 |
||
Withstand Voltage |
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC |
||
Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH |
||
Emc Emission |
Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020 |
||
Emc Immunity |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, EAC TP TC 020 |
||
Mtbf |
486.2K hrs min. MIL-HDBK-217F (25℃) |
||
Dimension |
32*102*125.2mm( L*W*H) |
||
Packing |
0.51Kg; 28pcs/15.3Kg/1.22CUFT |
||
Note |
|||
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. |
|||
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. |
|||
3. Tolerance : includes set up tolerance, line regulation and load regulation. |
|||
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |